How to Inspect Fire Doors: A Step-by-Step Checklist
A fire door is only as strong as its weakest part. A gap a few millimetres too wide, a seal painted over during redecorating, or a closer unhooked because the door ‘slams’ can turn a 30-minute barrier into an open route for smoke and flames. The good news is that learning how to inspect fire… Continue reading How to Inspect Fire Doors: A Step-by-Step Checklist
A fire door is only as strong as its weakest part. A gap a few millimetres too wide, a seal painted over during redecorating, or a closer unhooked because the door ‘slams’ can turn a 30-minute barrier into an open route for smoke and flames.
The good news is that learning how to inspect fire doors takes minutes, and most faults can be spotted with a simple gap gauge and a good look. This guide shows you how to inspect a fire door step by step, what a pass and a fail look like, and how often fire doors need checking under the Fire Safety (England) Regulations 2022.
Gerda Security has designed, manufactured, installed and maintained fire doorsets for over 25 years, so we know the importance of fire door checks and how each part is interconnected with the whole doorset and has an important role to play.
Quick Answer
- Find the certification label or plug, usually on the hinge edge or at the top.
- Check the gaps: typically 2–4mm at the top and sides, with a limit underneath that varies by doorset. Always confirm against the manufacturer’s test evidence.
- Make sure the intumescent and smoke seals are intact and unpainted.
- Confirm there are at least three hinges, all firmly fixed.
- Let the door close by itself: it should latch every time.
- Check the glazing, door leaf, and frame for damage.
- Test the locks, signage and any hold-open devices.
Why Fire Door Checks Matter
Fire doors hold back fire and smoke for a tested length of time, typically 30 or 60 minutes (shown as FD30S or FD60S). That time is important to maintain the integrity of the compartmentation or to enable means of escape.
Here’s the catch: a fire door is made up of parts that all have a role to play as a whole. The door leaf, frame, seals, hinges, door closer and glazing, all with their intumescents, work together. Break one link, and the fire rating is compromised, which is why a quick regular check is so invaluable.
There’s a legal side too. Building owners, landlords, and managers have a duty to keep fire doors in working order, and in some buildings the law sets exactly how often they must be checked.
What You Need Before You Start
- A torch.
- A phone (selfie mode makes the top edge easy to see).
- A fire door gap gauge or feeler gauge (to measure the gaps accurately).
- A checklist, such as the government’s fire doors checklist, which sets out what to look for on each door.
How to Inspect Fire Doors in 7 Steps
1. Find the certification label
Look along the hinge edge first for a label or plug. Some schemes, such as BlueSky, use a label with the scheme details, while BM TRADA Q-Mark uses a coloured plug. Others, such as BWF-Certifire, may be marked on the top edge.
Pass: A clear, readable label or plug from a recognised scheme.
Check further: No label, or one that’s been painted over or removed. Contact the manufacturer or a professional inspector.
A missing label doesn’t mean the door isn’t a fire door, or that it isn’t covered by a certification scheme. If you can identify the manufacturer, contact them. They may be able to confirm the door’s details and fire rating from their records.
Third-party certification isn’t a legal requirement, but it is best practice, as it’s the clearest way to prove a door will perform as it should. If you can’t confirm whether it’s a fire door, call in a professional fire door inspector. And don’t strip paint to look for a stamp.
2. Measure the gaps around the door
Check that the door closes properly into the door frame. Gaps should not be excessive. If you are unsure about a door gap, then refer back to the door manufacturer’s records. As a general guide, gaps should be a consistent 2–4mm.
The gap should also be even all the way round. And with the door shut, you shouldn’t see daylight underneath it.
| Gap location | Typical target | Fail sign |
| Top and hinge side | 2-4mm, consistent | Outside of 2-4mm |
| Latch side | 2-4mm, consistent | Uneven gap, or the door rubs and binds |
| Threshold (under the door) | Varies by threshold type, such as a drop-down smoke seal or a mobility threshold. Check the door manufacturer’s records for the correct limit. | Visible light, or a gap over the certified limit |
These are general figures. The door’s own certification and the manufacturer’s guidance always set the exact limits, so check those first if you can.
3. Inspect the intumescent and smoke seals
Look for the strips running along the door edge or set into the frame. Intumescent seals swell up when they get hot, sealing the gap so fire can’t get through. Brush or fin smoke seals stop cold smoke, which is often the bigger danger in the early stages of a fire.
Pass: Seals run continuously, sit firmly in their groove and are clean.
Fail: Seals that are painted over, snapped, peeling, or missing sections.
The most common failure is seals painted over during redecorating. Paint stops them from expanding, so they can’t do their job.
4. Check every hinge
Open the door and look at the hinges. These should have intumescents in place behind the hinges. There should be at least three hinges, firmly fixed, with every screw present, the right size, and not protruding.
Pass: Three or more solid hinges, no missing or loose screws.
Fail: Fewer than three hinges, loose or missing screws, or no intumescent behind the hinges. If none is fitted, check the manufacturer’s records to see what should be there.
5. Test the self-closer
For latched and unlatched doors, open the door fully and let it go. Then try again from about halfway, and once more from just a few centimetres open. Each time, the closer should shut the door completely flush into its frame on its own, overcoming any resistance from air pressure or intumescent seals, and hold it securely in the dead-centre closed position without sticking on the floor or the frame.
Pass: Closes and latches from every position, smoothly and fully.
Fail: Stops short, slams hard, has a disconnected closer arm, or is wedged open.
This step matters most. A fire door does nothing if it’s open.
6. Examine the glazing, door leaf and frame
- Glazing: fire-rated glass carries an etched mark in the corner. Check that it’s there, the glass isn’t cracked, and the beads holding it are secure.
- Door leaf: look for holes, splits, or damage, and for unapproved changes, such as a new letterbox, spyhole, cat flap, or holes drilled for cables.
- Frame: make sure it’s solidly fixed, and the gap between the frame and the wall is properly sealed. Look out for any additions, such as doorbells or cables fixed into or through the frame.
Pass: Fire-rated glass, an undamaged leaf and a solid, sealed frame.
Fail: Cracked or unmarked glass, unapproved holes or additions, or a loose frame.
7. Test the ironmongery, signage and hold-open devices
- Check that locks and latches work, and that the latch catches when the door closes.
- Confirm the right sign is in place, such as ‘Fire door keep shut’ or ‘Fire door keep locked’.
- If a magnetic hold-open device is fitted, check it releases the door when the fire alarm sounds.
Pass: The latch catches, the correct sign is fitted, and any hold-open device releases on alarm.
Fail: A faulty latch, a missing sign or a device that won’t release.
Fire Door Inspection Checklist
| Check | Pass | Fail |
| Certification | Label or plug present and readable | No label or plug. Check the manufacturer’s records or call an inspector. |
| Gaps | 2-4mm top and sides; within the manufacturer’s limit underneath | Uneven, too wide, or light visible |
| Seals | Continuous, firmly fixed, unpainted | Damaged, missing, or painted |
| Hinges | Three or more, all screws tight | Loose, missing screws, sagging door |
| Self-closer | Closes into door frame properly from any position | Stops short, disconnected, wedged open |
| Glazing, leaf, and frame | Fire-rated glass, no damage or alterations | Cracks, unapproved holes, loose frame |
| Ironmongery and signage | Latch works, correct signage, hold-open releases | Faulty latch, no sign, device won’t release |
Common Fire Door Faults to Look Out For
Most failed fire doors weren’t badly made. They were changed, damaged or worked around over time. These are the faults that come up again and again:
- Wedged or propped open. Convenient day-to-day, useless in a fire.
- Seals painted over. The paint stops them from swelling to close the gap.
- Bottoms planed down for new flooring. This leaves a threshold gap far beyond the certified limit.
- Closers disconnected because the door ‘slams’. The fix is adjusting the closer, not removing it.
- Missing or wrong hinge screws. The door can drop and twist in the heat of a fire.
- Replacement glass that isn’t fire-rated. The door can no longer hold back fire.
- DIY holes for cables, spyholes or cat flaps. Every hole is a shortcut for smoke and flames.
How Often Should Fire Doors Be Inspected in the UK?
In residential buildings over 11 metres tall in England, communal fire doors must be checked every three months, and flat entrance doors at least every 12 months, under the Fire Safety (England) Regulations 2022.
For other buildings in England, including smaller blocks of flats, HMOs and workplaces, the frequency is set by the fire risk assessment under the Regulatory Reform (Fire Safety) Order 2005. BS 8214, the code of practice for fire doors, recommends checking at least every six months, and more often for doors that get heavy use.
| Building and door type | Typical frequency | Basis |
| Residential over 11m, England: communal fire doors | Every 3 months | Fire Safety (England) Regulations 2022 |
| Residential over 11m, England: flat entrance fire doors | At least every 12 months (best endeavours) | Fire Safety (England) Regulations 2022 |
| Other multi-occupied residential and workplaces, England | Set by the fire risk assessment; at least every 6 months recommended | Fire Safety Order 2005, BS 8214 |
| High-traffic doors (corridors, stairwells, schools, hospitals) | Monthly or more often | Fire risk assessment |
Scotland, Wales, and Northern Ireland have their own fire safety laws. If your building is outside England, check the local guidance for your area.
Who is responsible for fire door checks being carried out?
The law calls them the ‘responsible person’. That’s usually the building owner, landlord, managing agent, or employer. They must make sure fire doors are maintained and checked, and that any faults are put right.
In blocks of flats, residents must also be told how fire doors work, why they need to stay shut, and that they shouldn’t be tampered with.
Routine checks vs professional inspections
The seven steps above are a routine check. They catch most problems, but they aren’t a substitute for a professional inspection.
| Routine check | Professional inspection | |
| Who | A trained caretaker, manager or landlord | A certified fire door inspector |
| What | A visual check of the seven points above | A detailed survey of every component against the door’s certification |
| How often | As your building’s rules require, often every 3 to 6 months | At least yearly, and after any failed check, damage or alteration |
| Result | A logged pass or fail for each door | A written report with photos and a schedule of repairs |
Always call in a certificated fire door inspector when a door has no certification, has been altered, or fails any part of your routine check. If the door then needs repairs or replacing, our fire door maintenance teams carry third-party certification for exactly this work.
What to Do If a Fire Door Fails
- Report it straight away to whoever owns or manages the building. Don’t walk past it.
- Keep the door closed while you wait for it to be fixed, and make sure nobody wedges it open.
- Log it with the date, the door’s location, what you found, and a photo.
- Get it fixed by someone competent. Small jobs, like adjusting a closer or replacing screws or seals with compatible certified parts, can often be done on site.
Bigger problems, such as a door with no certification, serious damage, or unapproved alterations, usually mean fitting a replacement fire doorset. Whatever the fix, avoid DIY repairs with uncertified parts. They can void the door’s fire rating entirely.
Keep a Record of Every Check
If it isn’t written down, it didn’t happen. Records are what regulators, fire services, and insurers ask to see, and they form part of a building’s ‘golden thread’ of safety information. For every door, log:
- The date of the check
- The door’s ID and location
- Who carried out the check
- What they found, with photos
- What action was taken, and when it was signed off
Paper logs work, but they’re easy to lose. Keep your inspection records somewhere safe and easy to find, alongside the rest of your building’s safety information. Digital fire door records such as Gerda’s G-Smart app hold the key information on each doorset, helping you maintain the golden thread of safety information for your building.
Keep Your Fire Doors in Safe Working Order
Now you know how to check fire doors; a five-minute look will catch most faults before they become a risk. Regular checks are a legal duty in many buildings, and a professional inspection fills in everything a visual check can’t.
Gerda’s certification teams maintain and replace fire doorsets, and our G-Smart app keeps the key information on each one for your building’s golden thread.

